CITY OF SAUK RAPIDS
ROOF VENTS
SECTION R806 ROOF VENTILATION
- R806.1
Ventilation required. Enclosed
attics and enclosed rafter spaces formed where ceilings are applied
directly to the underside of roof rafters shall have cross ventilation for
each separate space by ventilating openings protected against the entrance
of rain or snow.
- R806.2
Minimum area. The total net
free ventilating area shall not be less than 1 to 150 of the area
of the space ventilated except that the total area is permitted to be
reduced to 1 to 300, provided at least 50 percent and not more than 80
percent of the required ventilating area is provided by ventilators
located in the upper portion of the space to be ventilated at last 3
feet (914 mm) above eave or cornice vents with the balance of the
required ventilation provided by eave or cornice vents. As an alternative, the net free
cross-ventilation area may be reduced to 1 to 300 when a vapor barrier
having a transmission rate not exceeding 1 perm (57.4 mg/s.m2.Pa)
is installed on the warm side of the ceiling.
- R806.3
Vent clearance. Where eave or
cornice vents are installed, insulation shall not block the free flow of
air. A minimum of a 1-inch (25.4
mm) space shall be provided between the insulation and the roof sheathing
at the location of the vent.
Note
Ridge vents and gable louvered vents are an acceptable
alternative.
Any garage with an enclosed attic space will also need to be
ventilated.